Mecer 10000VA / 10000W ON-LINE UPS (with AVR,Monitoring Software + Cable & Built-in Surge Protection) - Black
Higher power density, more power output. Wider input range, higher efficiency. Ultra low noise, multiple configurable options. High quality LCD with wide view.
PHASE: Single phase input, single phase output.
Capacity: 10000 VA / 8000 W
Power
Apparent Power (KVA) / Active power (KW): 10KVA / 9KW
Mains
Voltage range: 120Vac-275Vac (phase to phase)
Current*: 52.6A max *The Max current is under 176Vac input, full rating load and empty battery charging.
Frequency range: 40Hz-70Hz
Power factor: 0.99
Output
Rating Voltage: 230Vac (+/-1%)
Rating Current: 45A
Frequency range: 50Hz x (1±1%); Follow main power in phase lock range
Power factor: 0.9
Output Overload
105%-125%, load transfer to bypass mode after 10 min (0-30℃ )
or 1min(30-40℃ );
125%-150%,load transfer to bypass mode after 30s;
Over 150%, load transfer to bypass after 0.5s
Load crest ratio: 3:1 (max)
THD: <2% (100% Line Load)
Dimension, D x W x H: 248mm x 500mm x 616mm
Net Weight: 62.1kg
Environmental and safety
EMC Standard: EN IEC 62040-2:2018 / EN 62040-2:2006 / IEC 62040-2:2016
Safety Standard: EN62040-1:2008+A1:2013
Operation temperature: 0-40℃
Store temperature: -25℃ to 55℃
Relative humidity: 20% to 90%
Altitude: <1000m
Altitude Rating load*Altitude correction factor.
Altitude(m): 1000 1500 2000 2500 3000 3500 4000 4500 5000
Altitude correction factor: 100% 95% 91% 86% 82% 78% 74% 70% 67%
Note: if UPS used over 1000m altitude, the rating must be derating according to above table.