Mecer 10000VA / 10000VW ON-LINE 3 Phase in/3 Phase out UPS (with AVR, Monitoring Software + Cable & Built-in Surge Protection) - Black
Description
Mecer Galleon II 3P/3P 10K / Online Tower 3 phase UPS PF1.0
ME-10K-GA33
Mecer - Mecer Galleon II 3P/3P 10K / Online Tower 3 phase UPS PF1.0, 3-phase in / 3-phase out, Up to 6 units in parallel, Zero transfer time Inverter to bypass, Pure Sine Wave, 9 hours recover to 90% capacity typical recharge time, 12v/9ah Battery Type
Overview:
Galleon II 3P/3P 10K-80K PF1, three-level inverter, common battery
Galleon II 3P/3P 10K-80K provides a better output power factor of up to 1.0 with higher performance and efficiency for critical applications. It is the same as the Galleon series with programmable power management outlets which can extend available battery time to critical devices by shutting down unnecessary devices. This Galleon II 3P/3P 10K-80K series is also suitable for laser printer and ultrasound system load.
Features:
True double-conversion
DSP technology guarantees high reliability
Output power factor 1.0
Active power factor correction in all phases
50hz/60hz frequency converter mode
ECO mode operation for energy saving
Emergency power off function (EPO)
Optional parallel operation
Smart battery charger design to optimize battery performance
Maintenance bypass available
Adjustable battery design
Specifications:
Product Code ME-10K-GA33
Model: Galleon II-3/3 10K(L)
Capacity: 10 KVA / 10 KW
Phase: 3-phase in/3-phase-out
Parallel Capability: up to 6 units in parallel
Input:
Voltage Range 190 - 520 VAC (3-phase) @ 50% load, 305 - 478 VAC (3-phase) @ 100% load
Nominal Voltage 3 x 380/ 400/ 415 VAC ( 3 Ph+N)
Frequency Range 40~70 Hz
Power Factor >= 0.99 @ 100% load
Output:
Output Voltage 3 x 360*/380/400/415 (3 Ph +N)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Transfer Time AC Mode to Battery Mode zero
Transfer Time Inverter to Bypass zero
Waveform (Batt. Mode) Pure Sine Wave
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ? 2 % THD (Linear Load), ? 5 % THD (Non-linear Load)
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Overload AC Mode 100-110% for 60 min, 110-125% for 10 min, >150% immediately
Overload Battery Mode 100-110% for 60 min, 110-125% for 10 min, >150% immediately
Efficiency:
Battery Mode 96%
ECO Mode 99%
AC Mode 96%
Battery:
Model-Battery Type Depending on the capacity of external batteries
Model-Charging Current (max.) 1A ~ 12A (Adjustable)
Model-Charging Voltage +/-136.5 VDC ± 10%
Model-Numbers (10+10) pcs
Battery Type 12V/9Ah
Charging Current (max.) 1A~12A (Adjustable)
Charging Voltage +/-136.5 VDC ± 10%
Numbers (10+10)pcs
Typical Recharge Time 9 hours recover to 90% capacity
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Environment:
Operating Temperature 0~40°C
Operating Humidity Noise Level Less than 55dB @ 1 Meter
Physical:
Standard Model Dimension, D X W X H (mm) 630 x 250 x 826
Standard Model Net Weight (kgs) 124
Long-run Model Dimension, D X W X H (mm) 630 x 250 x 826
Long-run Model Net Weight (kgs) 28
Management:
Optional SNMP Power management from SNMP manager and web browser
Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008, Windows 7 / / / 8 / / / 10, Linux, and MAC
What's in the box
1 x Mecer Galleon II 3P/3P 10K / Online Tower 3 Phase UPS PF1.0 - ME-10K-GA33